NiCr Grating (NiCr Plated) -Aluminum Series

Seismic Resistant Test

Seismic Resistant Test Purpose:: To prove that VERO's raised floor is capable to seismic resistant and demonstrable no damage of structure from the earth quake Location: Taiwan National Eearthquake Center Condition: Seismic g = 1.3 is applied on Vero's raised floor when loading is1400kgf/cm2 Result: No destruction in the structure is Shown after seismic test

    For any query send a message

    Call us: +880 1329662379

    S/N
    Item
    NiCrV60AG500
    NiCrV60AG700
    NiCrV60AG1000
    1-1 Material of Floor Tile

    N/A

    1-2 ESD of Floor Surface

    ≦ 0.1Ω

    2-1 Material of Panel

    Die-cast Aluminum

    2-2 Uniform Load
    1,000kgf/m2
    Deflection ≦1.0mm

    1,500kgf/m2
    Deflection ≦1.0mm

    2,000kgf/m2
    Deflection ≦1.0mm
    2-3 Concentrated Load
    500kgf/6.45cm2
    Deflection ≦2.0mm
    750kgf/6.45cm2
    Deflection ≦2.0mm
    1,000kgf/6.45cm2
    Deflection ≦2.0mm
    2-4 Ultimate Strength

    1,000kgf/6.45cm2

    1,500kgf/6.45cm2

    2,000kgf/6.45cm2

    2-5 Tolerance of Dimension
    2,000kgf/6.45cm2
    2-6 Tolerance of Thickness

    ± 0.10mm

    2-7 Tolerance of Flatness

    ± 0.20mm

    2-8 Tolerance of Diagonal

    Max. 0.50mm

    3-1

    Opening Rate

    50%

    3-2 Treatment Option

    Ni-Cr